Inverter (VFD) Fault Codes: Most Common Errors on Siemens, ABB, Delta, Yaskawa and Danfoss
Short answer: The most common inverter faults are overcurrent, DC link overvoltage, undervoltage and overtemperature. The code tells you what the drive detected, not why – motor, cable, load, supply and parameters must be checked together. If the fault persists with the motor disconnected, the problem is usually in the drive’s power stage and needs a board-level repair.
Common inverter fault codes by brand
Codes may vary by series and firmware; always confirm with your drive manual.
| Fault group | Siemens SINAMICS G120 | ABB ACS580 / ACS880 | Delta (C2000, MS300) | Yaskawa (A1000, GA500) | Danfoss VLT |
|---|---|---|---|---|---|
| Overcurrent | F30001, F07801 | 2310 | oc, ocA, ocd, ocn | oC | Alarm 13 |
| DC link overvoltage | F30002 | 3210 | ov, ovA, ovd, ovn | ov | Alarm 7 |
| DC link undervoltage | F30003 | 3220 | Lv | Uv1 | Alarm 8 |
| Heat sink / IGBT overtemperature | F30004 | 4210 | oH1 | oH, oH1 | Alarm 29 |
| Earth fault | — | 2330 | GFF | GF | Alarm 14 |
Overcurrent: causes and order of checks
- Acceleration ramp too short or high starting torque
- Mechanical jam, bearing problem or brake not releasing
- Short circuit or weak insulation in the motor cable
- Wrong motor data (no auto-tune)
- Faulty IGBT module, gate driver or current sensor
Disconnect the motor cables and run the drive unloaded. If the fault persists, the power stage is most likely defective; if it disappears, megger-test motor and cable and check the mechanics.
Overvoltage, undervoltage and overtemperature
Overvoltage usually appears during deceleration: lengthen the ramp and check the braking resistor and chopper. Undervoltage points to supply problems or aged DC link capacitors. Overtemperature is caused by dusty heat sinks, failed fans or poor cabinet ventilation.
When should you send the drive for repair?
- Overcurrent persists with the motor disconnected
- The drive blows fuses or the display stays dark
- Burn marks, swollen capacitors or a burnt smell
- The same fault returns despite parameter corrections
Frequently asked questions
Why does my inverter keep tripping on overcurrent?
Typical causes are short ramps, mechanical jams, motor cable or winding insulation faults, wrong motor data and a defective IGBT module. If it persists with the motor disconnected, the drive itself is faulty.
Can a faulty inverter be repaired?
Yes. IGBT, capacitor, power supply, driver and control board faults can usually be repaired at component level; Fiberfaz Elektronik tests repaired drives under load.
Fiberfaz Elektronik has been repairing industrial electronics brand-independently and with warranty at its workshop in Tuzla, Istanbul since 2012 (AC/DC and servo drive repair). Diagnosis is free; we serve Tuzla, Pendik, Gebze and the whole Asian side of Istanbul, with courier service across Türkiye. More: Inverter repair in Tuzla · Phone: +90 216 290 65 27 · WhatsApp: +90 537 592 67 70